Min./Max. Voltage calculation
The min./max. voltage calculation is used to define the minimum and maximum voltages occurring in a grid based on two worst-case scenarios:
- High Load: this scenario will be used to run a power flow calculation on all grids to define the minimum voltage of each grid.
- Low Load: this scenario will be used to run a power flow calculation on all grids to define the maximum voltage of each grid.
The minimum and maximum voltages
The worst-case scenarios can be defined on the Grid Data Updates page or when manually starting the min./max. voltage calculation.
INFO
The following features can take advantage of this through the setting Check voltage violations in sibling grids:
Check voltage violations in sibling grids
Sibling grids are grids that are electrically connected with each other only on the primary side of the transformer. For low-voltage grids this means a connection through the medium voltage grid.
Voltage violations in a sibling grid can occur under certain circumstances when adding additional load/generation in the grid that is to be evaluated or are already present in the base case.
When running a Hosting Capacity or Connection Request calculation the voltage violation in the sibling grids are considered as follows:
- The medium voltage grid is attached to the evaluated grid, including the slack bus of the sibling grids.
- The calculated voltage at the slack buses of the sibling grids must be within the range
, where and are the operational limits for overvoltage and undervoltage and and is the calculated voltage drop/rise from the min./max. voltage calculation.
If the calculated voltage at the slack bus falls outside of the range this means that a voltage violation in the sibling grid occurs (under the assumption of linearity).