Run static calculations with off-nominal voltages
To run a grid on an off-nominal voltage you need to...
- adjust the operational voltage of all network feeders, that feed the grid in an off-nominal voltage level.
- adjust the turns ratio on the primary and/or secondary side of the transformers, depending which side(s) is/are operated off-nominal.
Example
In this simple example, we have a 20kV medium voltage grid, operated at 22kV, fed by a 110kV high voltage grid, operated at 104kV. The screenshot shows, how the network feeder operational voltage and the transformer turns ratios have to be calculated, such that the operational voltages are met in a power flow calculation. To play around yourself, you can download our example Grid.
Manual adjustment of Operational voltage
Setup
In this example the grid model is set up as follows:
- Nominal voltage on the high voltage side is
. - Nominal voltage on the low voltage side is
. - The network feeder operates at an off-nominal voltage of
, which is equivalent to a relative voltage of . - The rated voltages of the transformer (on the center tap position) are
and . The transformer voltage specifications are summarized in the following two tables:
Rated Voltage | |
---|---|
HV | 11 +- 2x2.5% |
LV | 0.415 |
Tap no. | HV voltage [kV] |
---|---|
1 | 11.550 |
2 | 11.275 |
3 | 11.000 |
4 | 10.725 |
5 | 10.450 |
The grid with the above specifications can be downloaded and imported into Adaptricity.
Definitions
The following definitions will be required for the calculations that will follow in the next sections:
Transformer Voltage Ratio
The voltage ratio of a transformer is defined as the ratio of the primary voltage (high voltage) to the secondary voltage (low voltage):
Since in power systems we usually work with per unit (pu) values, we need to rewrite the above equation to incorporate the nominal voltages
The voltage ratio with per unit voltage values can then be written as:
where
The voltage ratio can also be written as
where
From both equations of
We will use this equation in the following sections.
INFO
In Adaptricity, we cannot directly change the rated voltage parameters
Power Flow
Running a Power Flow on the grid specified above, we can see that under load, the voltage at the low voltage (secondary) side of the transformer drops to
To increase the voltage on the low voltage side of the transformers, there are several options:
- adjust the operational voltage
of the network feeder - adjust the operational voltage of the transformer by changing the rated voltage
on the high voltage (primary) side of the transformer.
In the following, both options will be presented in detail. The goal is to achieve a voltage of
Adjusting the operational voltage of the network feeder
Assuming the rated voltages
For the setup above, we can calculate
and therefore
From the second equation for
Solving for
We can now update the network feeder operational voltage as part of a Grid Upgrade and re-run the Power Flow.
As can be seen, we were able to increase
INFO
With the simple equations above, we will not reach the desired
Adjusting the transformer tap position
We now assume that the operational voltage of the network feeder
To achieve a voltage increase of
We can now calculate the primary turns ratio
We can now update the primary turns ratio as part of a Grid Upgrade and re-run the Power Flow.
As can be seen, we were able to increase
We can calculate the exact rated voltage
This results in a primary turns ratio of
Running another Power Flow with the updated parameter, we see that the voltage