Skip to content

Short Circuit

This section allows users to configure parameters for short-circuit analysis, including impedance assumptions, voltage tolerances, and generator contributions. Short Circuit project settings

Zero-Sequence Impedance

  • Define a factor to relate zero-sequence impedance to positive-sequence impedance.
  • Used for calculating impedance in single-phase and two-phase-to-ground faults.
  • Default: 1 × positive-sequence impedance (conservative assumption).
  • Zero-sequence impedance of the overlying grid is neglected (R₀grid = ∞).

Voltage Tolerance

Affects the voltage correction factors (cₘᵢₙ and cₘₐₓ) for low-voltage buses:

  • 0%: cₘᵢₙ = 0.95, cₘₐₓ = 1.05
  • 10%: cₘᵢₙ = 0.9, cₘₐₓ = 1.1
  • IEC 60909-0:2001: cₘᵢₙ = 0.95, cₘₐₓ = 1.0

Short Circuit Duration

  • Set the duration (in seconds) used to calculate thermally equivalent short-circuit currents (Iₜˢ).

Branch Temperature

  • Select the assumed temperature of branches at the end of the short circuit:
    • 40°C (highest minimal currents)
    • 80°C
    • 160°F (lowest minimal currents, conservative)

Higher temperatures result in higher impedance and lower short-circuit currents, which may affect protection device performance.

Generator Contribution

  • Enable this option to allow generators to contribute to nearby short circuits.
  • By default, only the network feeder contributes.
  • Generators with specific connection types (e.g., inverter-based) can be included.

These settings help ensure accurate and standards-compliant short-circuit analysis for protection and planning purposes.